Cooling towers water has frequently been known as a source of infection in outbreaks of Legionnaires disease and a source of indoor air pollution. However, there have been a few reports on the presence of Legionella in cooling towers water and aerosols of various public facilities. This study was carried out to investigate the indoor and outdoor dis-tribution of Legionella spp and microbe from 132 cooling towers water of public facilities detected 1. pneumophila in Seoul and Gyeonggi-Do areas. The results showed that the Lpneumophila among the selected 132 cooling towers was detected mostly in July (12.0%), followed by August (4.0%) and June, September no-detected. The 1. pneumophiia in public facilities was detected mostly in department store (27.3%), followed by hospital (8.7%), office building (5.9%), big market (5.0%) and hotel, subway no-detected. The pH values of cooling towers water with presence of 1. pneumophila showed mostly 8.0 or higher (9.5%), followed by 7.0~8.0 (6.8%), lower 7.0 no-detected. The tem-perature of cooling towers water with presence of L pnemophila showed mostly 30℃ or higher (9.8%), followed by 26~30℃ (6.9%), lower 25℃ no-detected. The turbidity of cooling towers water with presence of 1. pneumaphila showed mostly 1-2 M (8.8%), followed by above 2 NTU (5.9%), lower 1 NTU no-detected. The correlation coef-ficient between indoor and outdoor concentration of microbes in public facilities showed 0.67 in Legionella spy. (p>0.05), 0.93 in bacteria (p<0.01), 0.94 in fungus (p<0.01), 0.98 in coilform (p<0.01), respectively.