상세검색
최근 검색어 전체 삭제
다국어입력
즐겨찾기0
커버이미지 없음
KCI등재 학술저널

스프링클러 반응시간 예측에 대한 화재모델의 비교

A Comparison of the Prediction of Sprinkler Response Time Applying Fire Models

  • 5

To evaluate the usability of compartment fire models for predicting sprinkler response time, fire experiment was conducted and measured sprinkler response time. The experimental data was compared with zone model "FASTLite"and field model "FDS"and field Model "SMARTFIRE" A Compartment fire conducted in a 2.4 m by 3.6 m by 2.4 m ISO 9705 room and measured H.R.R was approximately 100.3 kW. In test, Sprinkler activation temperature used is <TEX>$72^{\circ}c$</TEX> and responded at 198s. The output of FASTLite, SMARTFIRE and, FDS for this fire scenario were 209s, 183s, and 192s, respectively. As a results, prediction using FDS model approached to that of test very closely and other models showed good approximated results also.