화재하중을 통한 사찰의 화재 위험성 평가에 관한 연구

A Study on Fire Risk Assessment of the Temple Using Fire Loads

  • 62
커버이미지 없음

In this study, we considered the fire risk assessment of the temple using fire loads and the classification of combustibles. The building construction materials were classified as walls, beam-columns, floorings, ceiling panels and the loading combustibles were classified into fixed materials and movable materials. As a result, we confirmed that the total fire load of the Palsangjeon was <TEX>$368\;kg/m^2$</TEX>. The building construction materials accounted for approximately 93.8 percent of the total fire load and the loading combustibles accounted for approximately 6.2 percent.