상세검색
최근 검색어 전체 삭제
다국어입력
즐겨찾기0
커버이미지 없음
학술대회자료

평가시공불량을 모의한 배전급 케이블 종단부의 전기적 사고 연구

A Study on Electrical Accident of Distributing Cable Termination with Simulated Badness Construction

  • 2

This paper introduces experimental investigates of an electrical accident of the distributing cable termination with simulated badness construction. We prepared two termination kites, one is built-up type, the other is heat contraction type. Also, we manufactured cable termination that have simulated defect by badness construction and measured their insulation characteristics such as ac (35kV, 1min) and impulse (95kV, <TEX>$1.2{\times}50{\mu}s$</TEX>) withstand test. The influence of defects such as thickness and the gap between stress-con of housing and semi-conductor on insulating properties of the termination have been studied. The thickness decrease of insulator decreases ac breakdown strength. Dielectric breakdown traces of insulator that is damaged by knife displayed other shape. The gap of between housing and semiconductor deteriorates dielectric strength of insulator seriously.

로딩중