환기가 제한된 세 개 격실에서 Pool Fire에 대한 FDS 검증분석

Validation of FDS for Pool Fire in Three Rooms Connected to Ventilation Network

  • 11

This study aims to validate predictive capabilities of FDS for the pool fire in three rooms connected to ventilation network. The three rooms in real scale fire test facility are configured to be similar to that of nuclear power plant in size, ventilation condition, construction material, etc. Basically three rooms are confined to the other area except two open doors and two ventilation duct in each room. The real scale fire test was conducted with these conditions and the predictive capabilities of FDS will be validated by comparing FDS simulation results with experimental data from the temperature, heat flux, and concentration point of view. This study concludes that temperature from FDS is about 25 % lower deviation from the experiment, and heat flux from FDS is about 5% deviation.