초저온 냉동 시스템에서 2원냉동 팽창밸브의 압력 변화 특성에 관한 연구
A Study on the Characteristics of Pressure Variation of Cascade Refrigeration Expansion Valve in Cryogenic Refrigeration System
- 한국산업기술융합학회(구. 산업기술교육훈련학회)
- 산업기술연구논문지
- 산업기술교육훈련논문지 제19권 3호
- : KCI등재후보
- 2014.09
- 291 - 300 (10 pages)
The different evaporation temperatures and condensation temperatures, using a refrigerant with a characteristic for high temperature side and low temperature side Cycle to Cycle, each configured for a one side to the other Cycle in binary refrigeration to get the evaporation temperature of the low temperature impact test. Results could be confirmed that the other side Cycle 1 of the evaporator and the condenser from the outlet side of the heat exchanger by heat exchange with each other Cascade Cycle of one impact. In other words, although not a random operation Cycle primary components of the increase in the amount of open secondary expansion device to transfer more of the heat exchanger into the primary through the Cascade and this change increases 1 Conpressor suction side refrigerant status to ultimately 2 was confirmed by testing the arrival of a difference in the primary winding Cycle as well. Was confirmed that the evaporation temperature of the low temperature can be obtained affect each other through the Cascade Cycle device that is configured independently of the refrigerator through the two won in this experiment, respectively.
ᅵ. 서 론
II. 실 험
III. 실험결과 및 고찰
IV. 결 론
참고문헌