Objectives: Much attention has been paid to indoor air quality. Ventilation within schools is important because of indoor air quality and its effect on health and learning performance. In this study, we evaluated the carbon dioxide (CO₂) concentrations and ventilation rates in schools. Methods: This study measured the concentration of CO₂ in elementary, middle, and high school classrooms over six months. The seasons during the study were summer, fall, and winter. Sensor-based monitoring was used and the basic characteristics of the classroom were investigated. The body surface area of the students was used to calculate the CO₂ generation rate, and the air change per hour (ACH) was evaluated using mass balance modeling. Results: The average CO₂ concentration measured in most schools exceeded 1000 ppm. The ventilation rates varied from season to season. Compared to the recommended ventilation rate of 4.9 ACH, the roughly 3 ACH calculated in this study indicates that most schools possessed insufficient ventilation. Conclusions: The concentration of CO₂ in school classrooms could be an indicator of indoor air quality and can affect students learning ability. In this study, CO₂ concentrations exceeding the standard indicate a lack of ventilation along with problems with indoor air quality. Therefore, appropriate improvements are needed to overcome these problems.
I. 서 론
II. 연구 방법
III. 결 과
IV. 고 찰
V. 결 론
감사의 글
References