공냉식 증발기 팬의 동작 유·무에 대한 냉동시스템 성능분석

Performance Analysis Study of Condition Between Evaporator Fan Operating and not Operating at the Air Cooled Refrigerator

  • 0
cover.jpg

This study is that by using gas compression type refrigeration trainer, analysed factor which affect to performance of refrigeration system between evaporator fan operating and not operating condition at the low temperature operating condition of low pressure side. At the evaporator fan operating condition, analysing study result are high level conditions of condensing pressure, evaporating pressure, flash gas heat, refrigeration effect, Coefficient Of Performance(COP) and specially observed too high level of superheat. At the evaporator fan not operating condition, analysing research result are high level of compression work and wet compression. By conducting this study, had result that refrigerator operating performance have been big affected by condition between evaporator fan operating and not operating at the air cooled refrigerator.