클린룸 국소환경에서 오염원의 위험율에 대한 수치해석적 평가
Numerical evaluation of risk rates for contamination sources in a minienvironment
- 한국입자에어로졸학회
- Particle and aerosol research
- Vol.14 No.4
-
2018.01181 - 189 (9 pages)
- 2
In this study, the risk rates of different contamination sources of the contaminant in a minienvironment were analyzed through Computational Fluid Dynamics (CFD) simulation. The airflow pattern characteristics can only predict the qualitative variation of contaminant concentration, but cannot evaluate the quantitative variations in the risk rate of sources. From the results, the ambient contamination sources mainly affect wafers in the Front Opening Unified Pod (FOUP), whereas the internal contamination sources mainly affect wafers laid on the robot arm in the minienvironment. And the purging plenum system is very useful in protecting the wafers in the FOUP from contaminants transferred from the Fan Filter Unit (FFU). However, this system is unable to protect the wafers on the robot arm from internal contaminants and the wafers in the FOUP from sources of the interface between the FOUP and the minienvironment.
(0)
(0)